+44 (0) 800 123 4567 No.1 Abbey Road London, W1 ECH, UK
  • Chlorine Dioxide Generator CAPITAL CONTROLS МОДЕЛЬ G50

Chlorine Dioxide Generator CAPITAL CONTROLS МОДЕЛЬ G50

The CAPITAL CONTROLS® G50 chlorine dioxide generator is a two-chemical system, utilizing chlorine gas and 25 – 31 wt % sodium chlorite in the production of chlorine dioxide. A proven design, durable construction and the use of the best available corrosion-resistant materials assure efficient chlorine dioxide production, precise solution feeding, low maintenance and dependable operation for the life of the equipment.

KEY BENEFITS

  • All Vacuum System: The reagents are drawn into the generator by a vacuum, produced by an integral ejector. The chlorine dioxide gas produced by the generator is mixed with the ejector motive water and applied as a solution.
  • Capacities: standard chlorine dioxide generator units are available in a range of capacities from 5 kg/h to 50 kg/h of chlorine dioxide gas.

TECHNICAL INFORMATION

Capacity:

  • Up to 50 kg/h per skid
  • 10 to 1, flowmeter indication and control limits.

Connections (50 kg/h):

  • Ejector water inlet: 2" NPT (DN 50)
  • Cl2 gas inlet: 1" NPT (DN 25)
  • Sodium chlorite inlet: ½" NPT (DN 15)
  • Chlorine dioxide solution outlet: 2" NPT (DN 50)

Electrical Requirements (50 kg/h):

220 Vac, 50-60 Hz - 15A

Input/Output Signals:

  • 4-20 mADC inputs for process flow and/or residual feedback control
  • Contact inputs for chlorine leak, reagent reservoir low level, dilution water low pressure and remote start/stop.
  • Optional serial link RS485, RS422, RS232, MODBUS

Reagents:

  • Chlorine gas
  • 25% to 31% sodium chlorite wt. %

Dimensions:

1828.8 mm x 812.8 mm x 1828.8 mm

Standard Unit:

  • Instrumentation: Sight glass, vacuum gauge and Mag flowmeters for water and sodium chlorite.
  • Skid mounted, accessible, rigid tested plug-n-play for ease of installation.
  • PLC touch screen auto control

Materials of Construction:

  • Skid - 316 Stainless Steel, passivated
  • Piping - Schedule 80 PVC.
  • Reagent Control Valves - KYNAR, PVC

Recommended Accessories Available:

  • Chlorine Dioxide Solution Concentration Monitor: 0 - 4000 ppm.
  • Chlorine Dioxide Gas Detector: 0 - 100 ppm.
  • Chlorine Dioxide Residual Analyzer: 0 - 10 mg/L.
  • Serial Link RS485, RS232, RS422, MODBUS

DESCRIPTION OF OPERATION

The chlorine gas and sodium chlorite reagents are drawn into the generator under a vacuum, produced by an integral ejector. Reagent flow is controlled by Chloromatic™ valves, which are individually sized for each dosage capacity.
The chlorine dioxide gas is drawn out of the reaction chamber under a vacuum produced by the integral ejector where it is mixed with the ejector motive water and applied as a solution. The solution is passed through a sight glass for visual verification of product quality. The entire system is completely under vacuum from reagent draw into the generator to the ejector. If a low vacuum condition exists, valves will shut-off reagent flows to the generator. A low vacuum alarm contact is included. An automatically controlled system utilizes input signals for flow or residual.